The working pressure and temperature limits of ASME Code B31.9 - Building Services Piping
Sponsored Links
ASME B31.9 Building Services Piping applies to the following building services:
The working pressure and temperature limits of B31.9 can be summarized to:
| Service | Temperature Limit | Pressure Limit |
| Steam and condensate | maximum 366oF
(186oC),
minimum 0oF (-18oC) |
150 psig (1000 kPa) |
| Air, gases and vapors | maximum 200oF
(93oC),
minimum 0oF (-18oC) |
150 psig (1000 kPa) |
| Nonflammable Liquids | maximum 250oF
(121oC),
minimum 0oF (-18oC) |
350 psig (2300 kPa) |
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.