Heat loss from 1/2" to 4" copper pipes or tubes at various temperature differences between the pipe and the surrounding air, can be found in the table below:
| Nominal bore | Heat
loss for the fluid inside pipe
(W/m) |
Heat
loss for the fluid inside pipe
(Btu/hr.ft) |
|||||
| Temperature (oC) | Temperature (oF) | ||||||
| mm | inches | 40 | 55 | 72 | 70 | 100 | 130 |
| 15 | 1/2 | 21 | 32 | 45 | 22 | 34 | 47 |
| 22 | 3/4 | 28 | 43 | 60 | 29 | 45 | 53 |
| 28 | 1 | 34 | 53 | 76 | 36 | 56 | 79 |
| 35 | 1 1/4 | 41 | 64 | 89 | 43 | 67 | 93 |
| 42 | 1 1/2 | 47 | 74 | 104 | 49 | 77 | 108 |
| 54 | 2 | 59 | 93 | 131 | 62 | 97 | 136 |
| 67 | 2 1/2 | 71 | 111 | 156 | 74 | 116 | 162 |
| 76 | 3 | 83 | 129 | 181 | 87 | 135 | 189 |
| 108 | 4 | 107 | 165 | 232 | 111 | 172 | 241 |
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!