Heat loss from copper tubes at various temperature differences between tube and air

Sponsored Links

Values from the table below can be used to indicate the heat losses from uninsulated copper pipes:

Nominal bore Heat loss for fluid inside pipe
(W/m) (Btu/hr.ft)
(mm) (inches) 40oC 55oC 72oC 70oF 100oF 130oF
15 1/2 21 32 45 22 34 47
22 3/4 28 43 60 29 45 53
28 1 34 53 76 36 56 79
35 1 1/4 41 64 89 43 67 93
42 1 1/2 47 74 104 49 77 108
54 2 59 93 131 62 97 136
67 2 1/2 71 111 156 74 116 162
76 3 83 129 181 87 135 189
108 4 107 165 232 111 172 241

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The Piping ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The Piping ToolBox

The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.