Heat loss to surrounding air from insulated copper tubes
Sponsored Links
The heat loss from an insulated copper pipe or tube to the surrounding air can be found in the table below. The heat loss is based on a temperature difference of 55oC (oF) with an insulation thickness of 25 mm and a conductivity coefficient of k = 0.043 W/moC (0.3 Btu.in/ft2.hr.oF).
| Nominal bore | Heat loss for fluid inside pipe | ||
| (mm) | (inches) | (W/m) | (Btu/hr.ft) |
| 22 | 3/4 | 8 | 8 |
| 28 | 1 | 10 | 10 |
| 42 | 1 1/2 | 11.5 | 12 |
| 54 | 2 | 14.5 | 15 |
| 67 | 2 1/2 | 16 | 17 |
| 76 | 3 | 19 | 20 |
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.