Piping Systems and Applications! - Resources, Tools and Basic Information for Engineering and Design.
Metric Sizes of copper tubes to BS (British Standard) 2871:1972
Sponsored Links
The copper used in the manufacture of tubes is phosphorus deoxidized copper Cu-DHP defined by British Standard BS. 6017: 1981. This also corresponds to the ISO denomination Cu-DHP.
The minimum copper content is 99.85% and the residual phosphorus content is between 0.013 and 0.050%. This deoxidized copper is not affected by reducing atmospheres and consequently is well suited to welding and brazing. The density of copper is 8.9 g/cm3. its melting point is 1083 0C and its coefficient of linear expansion is 16.8 x 10-6 per 0C (between 20oC and 100oC).
(mm) |
Outside Diameter
(mm) |
Table X
Half hard light gauge tube |
Table Y
Half hard an annealed tube |
Table Z
Hard drawn thin wall tube |
|||
| Thickness
(mm) |
Maximum Working Pressure
(N/mm2) |
Thickness
(mm) |
Maximum Working Pressure
(N/mm2) |
Thickness
(mm) |
Maximum Working Pressure
(N/mm2) |
||
| 6 | 6 | 0.6 | 13.3 | 0.8 | 14.4 | 0.5 | 11.3 |
| 8 | 8 | 0.6 | 9.7 | 0.8 | 10.5 | 0.5 | 9.8 |
| 10 | 10 | 0.6 | 7.7 | 0.8 | 8.2 | 0.5 | 7.8 |
| 12 | 12 | 0.6 | 6.3 | 0.8 | 6.7 | 0.5 | 6.4 |
| 15 | 15 | 0.7 | 5.8 | 1 | 6.7 | 0.5 | 5 |
| 18 | 18 | 0.8 | 5.6 | 1 | 5.5 | 0.6 | 5 |
| 22 | 22 | 0.9 | 5.1 | 1.2 | 5.7 | 0.6 | 4.1 |
| 28 | 28 | 0.9 | 4 | 1.2 | 4.2 | 0.6 | 3.2 |
| 35 | 35 | 1.2 | 4.2 | 1.5 | 4.1 | 0.7 | 3 |
| 42 | 42 | 1.2 | 3.5 | 1.5 | 3.4 | 0.8 | 2.8 |
| 54 | 54 | 1.2 | 2.7 | 2 | 3.6 | 0.9 | 2.5 |
| 67 | 67 | 1.2 | 2 | 2 | 2.8 | 1 | 2 |
| 76.1 | 76.2 | 1.5 | 2.4 | 2 | 2.5 | 1.2 | 1.9 |
| 108 | 108.1 | 1.5 | 1.7 | 2.5 | 2.2 | 1.2 | 1.7 |
| 133 | 133.4 | 1.5 | 1.4 | 1.5 | 1.6 | ||
| 159 | 159.4 | 2 | 1.5 | 1.5 | 1.5 | ||
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!