Dimensions of copper tubes according ASTM B88M STANDARD SPECIFICATION FOR SEAMLESS COPPER WATER TUBE (METRIC) can be found in the table below:

Type A

Nominal Size
Outside Diameter
(mm)
Wall Thickness
(mm)
Tolerance +/-
Maximum Deviation at any Point
(mm)
Weight
(kg/m)
6 0.9 0.08 0.12
8 0.9 0.09 0.18
10 0.9 0.09 0.23
12 1.2 0.1 0.36
15 1.2 0.1 0.47
18 1.2 0.1 0.57
22 1.6 0.15 0.92
28 1.6 0.15 1.19
35 1.6 0.15 1.50
42 1.8 0.2 2.03
54 2.1 0.2 3.06
67 2.4 0.25 4.35
79 2.8 0.3 5.99
105 3.4 0.35 9.70
130 4.0 0.4 14.2
156 4.8 0.5 20.3
206 6.8 0.7 38.0
257 8.5 0.85 59.3
308 10.3 1 86.1

Type B

Nominal Size
Outside Diameter
(mm)
Wall Thickness
(mm)
Tolerance +/-
Maximum Deviation at any Point
(mm)
Weight
(kg/m)
6 0.7 0.07 0.10
8 0.8 0.08 0.16
10 0.8 0.08 0.21
12 0.9 0.09 0.28
15 1.0 0.1 0.39
18 1.0 0.1 0.48
22 1.1 0.1 0.65
28 1.2 0.1 0.90
35 1.4 0.15 1.32
42 1.5 0.15 1.71
54 1.7 0.15 2.50
67 2.0 0.15 3.65
79 2.3 0.2 4.95
105 2.8 0.25 8.04
130 3.1 0.3 11.0
156 3.5 0.3 15.0
206 5.0 0.35 28.2
257 6.3 0.5 44.4
308 7.1 0.65 60.0

Type C

Nominal Size
Outside Diameter
(mm)
Wall Thickness
(mm)
Tolerance +/-
Maximum Deviation at any Point
(mm)
Weight
(kg/m)
6 0.6 - 0.09
8 0.6 - 0.13
10 0.6 - 0.16
12 0.6 0.06 0.19
15 0.7 0.07 0.28
18 0.7 0.07 0.34
22 0.8 0.08 0.48
28 0.9 0.09 0.69
35 1.1 0.1 1.05
42 1.2 0.1 1.37
54 1.5 0.15 2.21
67 1.6 0.15 2.94
79 1.8 0.2 3.90
105 2.4 0.25 6.92
130 2.7 0.25 9.65
156 3.1 0.3 13.3
206 4.3 0.45 24.4
257 5.4 0.55 38.2
308 6.4 0.65 54.2

The B88M specification covers seamless copper water tube suitable for general plumbing, similar applications for the conveyance of fluids, and commonly used with solder, flared, or compression-type fittings. The type of copper water tube suitable for any particular application is determined by the internal or external fluid pressure, by the installation and service conditions, and by local requirements. Means of joining or bending are also factors that affect the selection of the type of tube to be used.

This specification is the metric companion of Specification B 88.

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The Piping ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The Piping ToolBox

The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1