The stress in fixed pipes depends on temperature
Sponsored Links
The stress in a fixed pipe depends on the temperature of the pipe and can be expressed as
σ = α E dt (1)
where
σ = stress (MPa, lb/in2)
α = linear expansion coefficient (m/moK, inch/inchoF)
E = modulus of elasticity of the piping material (MPa, lb/in2)
dt = temperature change from installation temperature (oC, oF)
The stress must not exceed maximum allowable stress for the chosen piping material. Be aware that with frequently change in temperature the stress cycle (with stress well below the maximum allowable limit) may fatigue the pipe.
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.