Piping Systems and Applications! - Resources, Tools and Basic Information for Engineering and Design.
Pressure Loss of Water Due to Friction in Copper Tubes Types K, L and M Copper Tube - ASTM B88
Sponsored Links
Pressure loss of water due to friction (major loss) in copper pipes, Types K, L and M tubes according ASTM B88, can be found in the tables below:
| Pressure Loss (psi per foot) | |||
| Flow
(GPM) |
Nominal or standard size (inches) | ||
| 1/4 | |||
| K | L | M | |
| 1 | 0.14 | 0.12 | |
| Pressure Loss (psi per foot) | |||
| Flow
(GPM) |
Nominal or standard size (inches) | ||
| 3/8 | |||
| K | L | M | |
| 1 | 0.04 | 0.02 | 0.02 |
| 2 | 0.13 | 0.08 | 0.08 |
| 3 | 0.28 | 0.18 | 0.16 |
| Pressure Loss (psi per foot) | |||
| Flow
(GPM) |
Nominal or standard size (inches) | ||
| 1/2 | |||
| K | L | M | |
| 1 | 0.01 | 0.01 | 0.01 |
| 2 | 0.04 | 0.03 | 0.02 |
| 3 | 0.07 | 0.06 | 0.05 |
| 4 | 0.13 | 0.11 | 0.09 |
| 5 | 0.19 | 0.16 | 0.13 |
| Pressure Loss (psi per foot) | |||
| Flow
(GPM) |
Nominal or standard size (inches) | ||
| 3/4 | |||
| K | L | M | |
| 2 | 0.01 | 0.01 | |
| 3 | 0.01 | 0.01 | 0.01 |
| 4 | 0.02 | 0.02 | 0.02 |
| 5 | 0.03 | 0.03 | 0.02 |
| 10 | 0.13 | 0.10 | 0.08 |
| Pressure Loss (psi per foot) | |||
| Flow
GPM |
Nominal or standard size (inches) | ||
| 1 | |||
| K | L | M | |
| 4 | 0.01 | 0.01 | |
| 5 | 0.01 | 0.01 | 0.01 |
| 10 | 0.03 | 0.03 | 0.02 |
| 15 | 0.07 | 0.06 | 0.05 |
| 20 | 0.10 | 0.08 | |
| Pressure Loss (psi per foot) | |||
| Flow
GPM |
Nominal or standard size (inches) | ||
| 1 1/4 | |||
| K | L | M | |
| 10 | 0.01 | 0.01 | 0.01 |
| 15 | 0.02 | 0.02 | 0.02 |
| 20 | 0.04 | 0.04 | 0.03 |
| 25 | 0.06 | 0.05 | 0.05 |
| 30 | 0.08 | 0.07 | 0.07 |
| Pressure Loss (psi per foot) | |||
| Flow
GPM |
Nominal or standard size (inches) | ||
| 1 1/2 | |||
| K | L | M | |
| 15 | 0.01 | 0.01 | 0.01 |
| 20 | 0.02 | 0.02 | 0.01 |
| 25 | 0.02 | 0.02 | 0.02 |
| 30 | 0.03 | 0.03 | 0.03 |
| 35 | 0.05 | 0.04 | 0.04 |
| 40 | 0.06 | 0.05 | 0.05 |
| 45 | 0.06 | ||
| Pressure Loss (psi per foot) | |||
| Flow
GPM |
Nominal or standard size (inches) | ||
| 2 | |||
| K | L | M | |
| 25 | 0.01 | 0.01 | |
| 30 | 0.01 | 0.01 | 0.01 |
| 35 | 0.01 | 0.01 | 0.01 |
| 40 | 0.02 | 0.01 | 0.01 |
| 45 | 0.02 | 0.02 | 0.02 |
| 50 | 0.02 | 0.02 | 0.02 |
| 60 | 0.03 | 0.03 | 0.03 |
| 70 | 0.04 | 0.04 | 0.04 |
The pressure loss is based on the Hazen-Williams formula.
Copper Tubes Types K, L and M - Dimensions
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.
We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.
5 12 1
View Engineering, Design and Construction news in the absolute FREE Automatic WebSite Viewer. Engineering Breaking News!