The tables below can be used for propane gas pipe sizing.

Steel Pipe - Schedule 40

Capacity of Pipe (kW)
Pipe Size
(in)
Pipe Length (m)
3 6 12 24 50
1/2 70 48 33 22 15
3/4 145 100 69 47 32
1 274 188 130 89 60
1 1/4 560 387 265 182 123
1 1/2 840 580 400 274 184
2 1625 1117 768 527 354
2 1/2 2590 1780 1223 841 565
3 4580 3145 2160 1487 1000
4 9340 6415 4410 3030 2040
5 16900 11615 7980 5485 3690
6 27360 18800 12920 8880 5970
8 56220 38640 26560 18250 12270

Copper Tubing - type K

Capacity of Pipe (kW)
Nominal Pipe Size (O.D)
(in)
Pipe Length (m)
3 6 12 24
1/4 (3/8) 11 7 5 3
3/8 (1/2) 22 15 11 7
1/2 (5/8) 45 31 21 15
5/8 (3/4) 79 54 37 26
3/4 (7/8) 112 77 53 36
1 (1 1/8) 239 165 113 77
1 1/4 (1 3/8) 430 295 203 140

Copper Tubing - type L

Capacity of Pipe (kW)
Nominal Pipe Size (O.D)
(in)
Pipe Length (m)
3 6 12 24
1/4 (3/8) 12 8 5 4
3/8 (1/2) 26 18 12 8
1/2 (5/8) 50 34 23 16
5/8 (3/4) 83 57 39 27
3/4 (7/8) 128 88 60 41
1 (1 1/8) 258 177 122 83
1 1/4 (1 3/8) 450 308 211 145

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The Piping ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The Piping ToolBox

The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1