Calculation formula spring operated relief valves in liquid systems
Sponsored Links
The minimum discharge area of spring operated relief safety valves in liquid systems can be calculated as
A = q SG1/2 / (28.14 Kbp Kvisc dp1/2)
where
A = discharge area (Square Inches)
q = relieving capacity (Gallons per Minute)
SG = Specific Gravity
Kbp = capacity correction for back pressure - 1.0 for atmospheric pressure systems
Kvisc = correction factor due to velocity - 1.0 for most water systems
dp = differential pressure - set pressure (psig) + over pressure (psig) - back pressure (psig)
Sponsored Links
Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!
Translate this page to
Spanish
French
German
Italian
Dutch
Norwegian
© The Piping ToolBox
The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.