The minimum discharge area of pilot operated relief safety valves in liquid systems can be calculated as

A = q SG1/2 / (36.81 Kvisc dp1/2)

where

A = discharge area (Square Inches)

q = relieving capacity (Gallons per Minute)

SG = Specific Gravity

Kvisc = correction factor due to velocity - 1.0 for most water systems

dp = differential pressure - set pressure (psig) + over pressure (psig) - back pressure (psig)

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The Piping ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The Piping ToolBox

The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.