PVDF Pipes - Support Spacing

Support spacing for PVDF pipes

Sponsored Links

Maximum support spacing for PVDF - PolyVinylidene Fluoride - pipes depends on the operating temperature. Maximum spacing between supports at different temperatures can be found in the tables below:

PVDF - Wall Schedule 40 - Support Spacing (feet)
NPS
(inches)
Operating Temperature (oF)
80 100 1401)
1/2 3 1/2 3 1/2 2
3/4 4 3 1/2 2 1/2
1 4 4 2 1/2
1 1/2 4 1/2 4 1/2 2 1/2
2 4 1/2 4 1/2 2 1/2

PVDF - Wall Schedule 80 - Support Spacing (feet)
NPS
(inches)
Operating Temperature (oF)
80 100 1401)
1/2 4 1/2 4 1/2 2 1/2
3/4 4 1/2 4 1/2 3
1 5 4 1/2 3
1 1/2 5 1/2 5 3
2 5 1/2 5 3

1) For temperatures above 140oF continuous support is needed.

PVDF is recognized by its high mechanical strength and excellent chemical resistance even at higher temperatures.

Sponsored Links


ToolBox ShortList

Difficult to find your favorite ToolBox page? Add a link to the page in your own personal Shortlist!

Add this Page!Delete the ShortList!

Google
Web The Piping ToolBox

Free Translation
Translate this page to Spanish French German Italian Dutch Norwegian

© The Piping ToolBox

The content in The Piping ToolBox is copyrighted but can be used with NO WARRANTY or LIABILITY. Important information should always be double checked with alternative sources. All applicable national and local regulations and practices concerning this aspects must be strictly followed and adhered to.

We appreciate any comments and tips on how to make The Piping ToolBox a better information source. Please contact us by email if You find any faults, inaccurate, or otherwise unacceptable information.

Editor email

5 12 1